CN
  • Outdoor Composite Terminal
    Outdoor Composite Terminal

Outdoor Composite Terminal

Our company produces Ankura-YJZWFY4 type composite bushing outdoor terminals with rated voltages of 48/66kV, 64/110kV, 76/138kV, 127/220kV, 290/500kV (300/500kV). The external insulation composite bushing is composed of epoxy glass fiber tubes and external weather-resistant insulating silicone rubber skirts. The bushing is filled with insulating agent. It adopts a special structure for sealing, ensuring reliable sealing performance. The stress cone is injection-molded with colorless transparent liquid rubber, and the stress cone adopts a patented structure, which is easy to install and has reliable grounding. The product has over fifteen years of operation experience and is suitable for various operating environments, with reliable performance.

Features
  • 48/66kV, 64/110kV, 76/138kV, 127/220kV porcelain bushings are filled with insulating agents. Liquid or solid insulating agents can be configured according to user requirements, and oil-type or solid insulation products can be provided.
  • Pressure relief function and insulation oil level monitoring function can be configured according to user requirements, further enhancing the safety and intelligence of the product.
  • It is applied in areas far from densely populated areas, high-pollution environments, and coastal regions.
  • The structural dimensions of the end outlet hardware can be configured according to user requirements.
Main Parameters
Outdoor Composite Terminal
Outdoor Composite Terminal
Technical Parameters
Technical Specifications 110K(66kV) 220kV 500kV
Adaptation of cable conductor cross-section (mm2) 240~2500 400~2500 800~3000
Product reference weight (kg) 128 370 1625
Material of rubber part (stress cone) Silicone rubber Silicone rubber Silicone rubber
Inner insulating filler Polyisobutylene / Solid Insulating Agent Polyisobutylene / Solid Insulating Agent Polyisobutylene
Product reference size Contamination level e e e
Terminal height A 2019 3142 5630
Pipe height h 1320 2400 460
Height from the outlet end to the installation platform B 1805 3035 5335
Plate dimensions (length x width) C 400×400 460×460 830×830
Maximum outer diameter of the pillar insulator Ф2 102 160 145
Distance between installation holes of the pillar insulator L2 320 390 450×450/750×750
Conductor connection method Confined pressure Confined pressure Confined pressure