CN
  • GIS / Transformer Terminal
    GIS / Transformer Terminal

GIS / Transformer Terminal

The Ankura-YJZGG/YJZGGCB type dry-type insulation GIS (transformer) terminals with rated voltages of 48/66kV, 64/110kV, 76/138kV, 127/220kV, 290/500kV (300/500kV) adopt a combined structure of pre-made stress cones and epoxy sleeves. The spring clamping device presses the pre-made stress cones against the wall of the epoxy sleeve, maintaining the pressure between the rubber stress cone and the cable insulation and the inner cavity of the epoxy sleeve within a reliable range, which can adapt to the extreme high and low temperatures in domestic and international operating environments. The product has a compact structure, excellent performance, convenient installation, and simple maintenance. It has over fifteen years of operation experience and is reliable in performance.

Features
  • 48/66kV, 64/110kV, 76/138kV, 127/220kV conductor connection in two ways: crimping, plug-in type.
  • Users can choose according to their needs.
  • The product can be used for the connection of transformers and cables, with a plug-in structure for connection, making the product installation more convenient.
  • The product has extremely high electrical sociality and reliability.
Main Parameters
GIS / Transformer Terminal
GIS / Transformer Terminal
Technical Parameters
Technical Specifications 66kV 110kV 220kV 500kV
Adaptation of cable conductor cross-section (mm2) 185~1600 240~2500 240~2500 800~3000
Reference weight of the product (short/long type) (kg) 45 58/68 148/168 290/320
Material of rubber part (stress cone) Silicone rubber Silicone rubber Silicone rubber Silicone rubber
Product reference dimensions L1 825 990/1277 1195/1535 1769/2209
L2 105 110 130 185
L3 310 470/757 620/960 960/1400
L4 / 18 25 25
Ф1 99 110 200 250
A Φ80 Φ80 Φ110 Φ110
B Φ298 Φ348 Φ620(Φ500) Φ690
C Φ270 Φ320 Φ582(Φ475) Φ640
D Φ245 Φ298 Φ559(Φ454) Φ617
E Φ188 Φ208 Φ356 Φ470
F 257 276 357 473
Conductor connection method Insertion and removal Insertion/Compression Insertion/Compression Insertion/Compression
Switch connection execution standard GB/T22381、IEC62271、IEC60859